HP to amps calculator

For branch-circuit sizing, NEC 430.6(A)(1) says to use the table full-load current, not the nameplate. This tool gives both the table value and a calculated estimate.

VC-9 motor currentNEC 430.248 · 430.250
Motor
%
NEC table full-load current8A
Conductors ≥ 125% = 10 AMin copper 14 AWG (75 °C)Max inverse-time breaker 20 ACalculated from η & PF 4.5 A

Conductor size assumes 75 °C terminals, 30 °C ambient and a short run. The breaker figure is the maximum for a squirrel-cage motor per Table 430.52 (250% of FLC, rounded up to a standard size per 430.52(C)(1) Exception 1). A smaller breaker is fine if the motor starts. Overload protection (430.32) is sized from the nameplate current, usually 115–125%. Have a licensed electrician size and install motor circuits.

Table current vs. calculated current

NEC 430.6(A)(1) says to size motor branch-circuit conductors and short-circuit protection from the full-load current in Tables 430.247–430.250, not from the nameplate and not from a calculation. The tables are deliberately conservative so a replacement motor with a slightly different nameplate still fits the circuit.

The calculated figure uses I = hp × 746 ÷ (η × V × PF) (single-phase) or ÷ (1.732 × V × η × PF) (three-phase). It's useful for estimating energy use, not for sizing.

Three-phase full-load current, NEC Table 430.250 (selection)

hp208 V230 V460 V575 V
1/22.42.21.10.9
3/43.53.21.61.3
14.64.22.11.7
1-1/26.6632.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
7-1/224.222119
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552
601691547762
752111929677
10027324812499
125343312156125
150396360180144
200528480240192

Single-phase full-load current, NEC Table 430.248

hp115 V230 V
1/64.42.2
1/45.82.9
1/37.23.6
1/29.84.9
3/413.86.9
1168
1-1/22010
22412
33417
55628
7-1/28040
1010050

For 200 V and 208 V single-phase motors, NEC Table 430.248 notes to increase the 230 V current by 15% and 10% respectively.

Questions people ask

How many amps does a 1 hp motor draw?

Per NEC Table 430.248, a 1 hp single-phase motor draws 16 A at 115 V and 8 A at 230 V. Per Table 430.250 a 1 hp three-phase motor draws 4.2 A at 230 V and 2.1 A at 460 V.

Why use the NEC table instead of the nameplate?

NEC 430.6(A)(1) requires the table full-load current for sizing conductors and short-circuit protection. The nameplate current is used for overload protection (430.32).

How is motor conductor ampacity sized?

NEC 430.22: at least 125% of the table full-load current for a single continuous-duty motor.