Wire size and ampacity chart

Base ampacity for insulated conductors rated up to 2,000 V, no more than three current-carrying conductors in a raceway, cable or earth, at 30 °C (86 °F) ambient. Adjust for real conditions before choosing a size.

VC-5 ampacity tableNEC 2023 TABLE 310.16
Show

Need a size for your exact conditions? Use the wire size calculator, which applies temperature, bundling and voltage drop.

SizeCopper (A)Aluminum / Cu-clad Al (A)mm²Max OCPD 240.4(D)
60 °C75 °C90 °C60 °C75 °C90 °C
14 AWG152025———2.08Cu 15 A
12 AWG2025301520253.31Cu 20 A · Al 15 A
10 AWG3035402530355.261Cu 30 A · Al 25 A
8 AWG4050553040458.367—
6 AWG55657540505513.3—
4 AWG70859555657521.15—
3 AWG8510011565758526.67—
2 AWG95115130759010033.62—
1 AWG1101301458510011542.41—
1/0 AWG12515017010012013553.49—
2/0 AWG14517519511513515067.43—
3/0 AWG16520022513015517585.01—
4/0 AWG195230260150180205107.2—
250 kcmil215255290170205230127—
300 kcmil240285320195230260152—
350 kcmil260310350210250280177—
400 kcmil280335380225270305203—
500 kcmil320380430260310350253—
600 kcmil350420475285340385304—
750 kcmil400475535320385435380—
1000 kcmil455545615375445500507—

NEC 2023 Table 310.16: insulated conductors rated up to and including 2,000 V, 60 °C through 90 °C, not more than three current-carrying conductors in a raceway, cable or earth (directly buried), 30 °C (86 °F) ambient. mm² is the metric area from Chapter 9 Table 8. The 2026 NEC adds values for 16 AWG copper and 14 AWG copper-clad aluminum; this chart follows the 2023 edition that most jurisdictions currently enforce.

This is the starting point, not the answer. Use the column your terminals allow (usually 60 °C for 100 A and below, 75 °C above, per 110.14(C)), NM-B cable at 60 °C (334.80), then apply temperature and bundling corrections. Aluminum needs AL-rated terminals.

Temperature correction, Table 310.15(B)(1)

Multiply the table ampacity by this factor when the ambient temperature isn't 30 °C (86 °F). Rooftops in sunlight, attics and boiler rooms often run far hotter.

Ambient °C (°F)60 °C75 °C90 °C
21–25 (70–77)1.081.051.04
26–30 (78–86)1.001.001.00
31–35 (87–95)0.910.940.96
36–40 (96–104)0.820.880.91
41–45 (105–113)0.710.820.87
46–50 (114–122)0.580.750.82
51–55 (123–131)0.410.670.76
56–60 (132–140)—0.580.71

More than three current-carrying conductors, Table 310.15(C)(1)

Current-carrying conductorsMultiply ampacity by
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Equipment grounding conductors don't count. A neutral that carries only the unbalanced current of other conductors in the same circuit usually doesn't count either (310.15(E)).

Worked example

6 AWG copper THHN in a conduit through a 38 °C space with five current-carrying conductors, landing on 75 °C terminals: 75 A (90 °C column) × 0.91 × 0.80 = 54.6 A. That is below the 65 A 75 °C limit, so 54.6 A is the allowable ampacity.

Questions people ask

How many amps can 12 gauge wire carry?

NEC Table 310.16 lists 12 AWG copper at 20 A (60 °C), 25 A (75 °C) and 30 A (90 °C). NEC 240.4(D) limits its overcurrent protection to 20 A, so it goes on a 20 A breaker.

How many amps can 10 gauge wire carry?

30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C. 240.4(D) limits the breaker to 30 A.

How many amps can 14 gauge wire carry?

15 A at 60 °C, 20 A at 75 °C, 25 A at 90 °C, and 240.4(D) limits the breaker to 15 A.

Why is aluminum rated lower than copper?

Aluminum has about 61% of copper’s conductivity, so the same size heats more at a given current. Aluminum is typically one to two sizes larger for the same ampacity, and needs terminals rated for aluminum (AL or CU/AL).