Transformer calculator

Enter the transformer rating and voltages to get full-load current on both sides and the turns ratio, or enter your load to find the next standard kVA size.

VC-12 transformerkVA · FLA · RATIO
Transformer
kVA
V
V
Full-load current54.1 / 124.9A
Primary 54.1 ASecondary 124.9 ATurns ratio 2.308 : 1

Size a transformer for a load

A
V
Suggested standard size75kVA
Load 36 kVA+25% headroom 45 kVA

25% headroom is a common design margin, not a code rule; the actual size should come from a load calculation (NEC Article 220) and the manufacturer's data. Overcurrent protection per NEC 450.3(B) and secondary conductor rules per 240.21(C) need a qualified designer.

Transformer formulas

Single-phase: I = kVA × 1000 ÷ VThree-phase: I = kVA × 1000 ÷ (1.732 × VLL)Turns ratio = Vprimary ÷ Vsecondary = Isecondary ÷ Iprimary

Example: a 75 kVA, 480 V delta to 208Y/120 V transformer carries 75,000 ÷ (1.732 × 480) = 90.2 A on the primary and 208.2 A on the secondary. The turns ratio is 2.31 : 1.

Standard kVA sizes

Single-phase: 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250 kVA. Three-phase: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000 kVA. Availability varies by manufacturer.

Questions people ask

How do I calculate transformer full-load current?

Single-phase: I = kVA × 1000 ÷ V. Three-phase: I = kVA × 1000 ÷ (1.732 × V). A 45 kVA, 480–208Y/120 V transformer carries 54.1 A primary and 124.9 A secondary.

What are standard transformer sizes?

Common dry-type sizes: single-phase 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167 kVA; three-phase 15, 30, 45, 75, 112.5, 150, 225, 300, 500 kVA. Check the manufacturer’s catalog.

How are transformer overcurrent devices sized?

NEC 450.3(B) sets maximum primary and secondary protection as a percentage of rated current, depending on voltage and whether secondary protection is provided. Have the design checked by a qualified person.