kVA to amps calculator

Enter apparent power in kVA and the voltage. kVA already includes power factor, so no PF is needed.

VC-2 converterkVA → A
Supply
kVA
V
Full-load current90.21A
I = kVA × 1000 ÷ (√3 × V)Breaker: 100 A non-continuous · 125 A if it runs 3 h+
Breaker figures are the next standard size from NEC 240.6(A), with 125% for continuous loads (210.20(A)). The wire must be rated for the breaker, and motors and HVAC follow different rules. See the breaker size calculator.

Quick reference

kVA208 V 3-ph480 V 3-ph240 V 1-ph
15 kVA41.6418.0462.5
30 kVA83.2736.08125
45 kVA124.954.13187.5
75 kVA208.290.21312.5
112.5 kVA312.3135.3468.8
150 kVA416.4180.4625
225 kVA624.5270.6937.5
300 kVA832.7360.81,250
500 kVA1,388601.42,083

Full-load current for common three-phase transformer sizes.

The formulas

Single-phase: I = kVA × 1000 ÷ V and kVA = V × I ÷ 1000

Three-phase: I = kVA × 1000 ÷ (1.732 × VLL) and kVA = 1.732 × VLL × I ÷ 1000

kVA is apparent power. It is what transformers, generators and UPS units are rated in, because their heating depends on current whatever the power factor. To get real power: kW = kVA × PF.

Using the result safely

  • Nameplate current beats a calculation. If the equipment lists amps, use that figure.
  • For a load that runs 3 hours or more (EV charger, water heater, space heater), the NEC sizes conductors and breakers at 125% of the load.
  • To pick the conductor for the current you found, go to the wire size calculator; for long runs check the voltage drop.

Questions people ask

How many amps is 75 kVA at 480 V three-phase?

75,000 ÷ (1.732 × 480) = 90.2 A on the primary. On a 208 V secondary it is 208.2 A.

Why is there no power factor in kVA to amps?

kVA is apparent power: volts × amps with no power factor applied. Current depends only on kVA and voltage.

kVA vs kW: what is the difference?

kW is real power that does work; kVA is apparent power the wiring must carry. kW = kVA × PF.